Fiberglass Filtration Systems
Service Flow Rates
Single Flow Rate GPM
Twin Flow Rate GPM
Plumbing
Continuous
Continuous
Peak
Continuous
Continuous
Peak
Back Wash Connection
MG/FE/H2S
FE Only
FE Only
MG/FE/H2S
FE Only
FE Only
Model
Tank Size
Flow Rate
(inches)
@3gpm/SqFt
@5gpm/SqFt
@7gpm/SqFt
@3gpm/SqFt
@5gpm/SqFt
@7gpm/SqFt
IC-13
1354
10
1” or 1.25”
2.8
4.6
6.4
5.6
9.2
12.8
IC-14
1465
10
1.25”
3.4
5.3
7.5
6.8
10.6
15
IC-16
1665
15
1.25”
4
7
10
8
14
20
IC-18
1865
20
1.5” or 2”
5
9
12
10
18
24
IC-21
2162
25
1.5” or 2”
7
12
17
14
24
34
IC-24
2472
35
1.5” or 2”
9
16
22
18
32
44
IC-30
3072
50
2” or 3”
15
25
34
30
50
68
IC-36
3672
70
2” or 3”
21
35
49
42
70
98
IC-42
4272
115
3”
29
48
67
58
96
134
IC-48
4872
150
3”
38
63
88
76
126
176
Fiberglass Aeration Tanks
Steel Aeration Tanks Top Inlet & Bottom Outlet
Service Flow Rates (GPM)
Flow Rate
Tank
Contact
ICRCC
Flow Rates
Size
Gallons
Continuous
Peak
Model Number
Model
Continuous
Peak
GPM 1
GPM 2
1354
6
9
30 x 60
133
44
67
60407-607E/HD
1465
9
13
36 x 60
196
65
98
60407-607E/HD
1665
11
16
42 x 60
271
90
136
7G5
1865
15
22
48 x 60
365
121
183
7G5
2162
18
27
54 x 60
469
156
235
7G5
2472
26
40
60 x 60
588
196
294
7G7
3072
41
73
66 x 60
722
241
361
7G7
3672
54
81
72 x 60
875
292
438
7G7
1. Designed to provide a minimum of 3 minutes contact time at the flow rate shown. Use this
4272
75
112
rating for iron and manganese and/or hydrogen sulfide removal.
4872
100
150
2. Designed to provide a minimum of 2 minutes contact time at the flow rate stated. Use this
rating for iron removal only.
Flow Rates
Continuous Flow - Where a steady flow of water is flowing throughout the filter for 30 minutes or longer.
Peak Flow - Where interrupted patterns of water usage occur at less than 30 minute intervals.
Performance
For Iron to oxidize and precipitate within the filter system, the influent water must have:
1. A pH of at least 6.8. If the pH is below this, it should be increased.
2. No organics such as tannins. Organics may prevent the oxidation process from occurring.
3. Sequestering agents such as poly phosphates must not be present. They also prevent the oxidation process from occurring.
4. Manganese is not effectively removed by oxidation filtration, unless the pH is 8.5 or higher. When it is not practical to in -
crease the pH to this level, manganese should be removed by ion exchange.
5. If Hydrogen Sulfide is present, it will consume the oxygen in the water very quickly, leaving less available for oxidizing and
precipitating the iron. Depending on the water analysis, flow rates greater than 3 gpm/SqFt. maybe possible. Using a larger
aeration tank(s) or more frequent recharge cycles and a modified media bed will improve the results. Always use the special
media bed when H2S is present above 2ppm.
Sizing Instructions
1. Select the filter(s) that meet both your service and backwash rate requirements. Additional capacity can be added as triplex
and quad systems.
NOTE: Filter backwash rates are always higher than service flow rates. The available backwash water in gallons per minute
at 30 psi continuous will limit the size of the filter for application. Multiple filters are also necessary when
continuous supply is required. Backwashing and rinsing with filtered water is recommended for higher water quality.
2. Select the correct aeration tank that meets the service flow rate of the system
3. Steel tank and/or custom design systems available upon request.
7/30/12-LBRY