Model
G, G+
H, H+
J, J+
K, K+
Pro50
Flow rates
Rated flow at dose 30 mJ/
cm 2 @ 95% UVT
23gpm (87 lpm)
45 gpm (170 lpm)
45 gpm (170 lpm)*
80 gpm (303 lpm)
--
Rated flow at dose 40 mJ/
cm 2 @ 95% UVT
17 gpm (64 lpm)
35 gpm (132 lpm)
45 gpm (170 lpm)
--
--
Rated flow for USEPA
UVDGM 2006 protocol
--
--
--
--
50 gpm (189 lpm)
operating Parameters
Operating pressure
10 - 100 psi (689 kPa)
10 - 100 psi (689 kPa)
10 - 100 psi (689 kPa)
10 - 100 psi (689 kPa)
10 - 100 psi (689 kPa)
Ambient air temperature
32°F (0°C) - 104°F (40°C)
32°F (0°C) - 104°F (40°C)
32°F (0°C) - 104°F (40°C)
32°F (0°C) - 104°F (40°C)
32°F (0°C) - 104°F (40°C)
Ambient water temperature
39°F (4°C) - 104°F (40°C)
39°F (4°C) - 104°F (40°C)
39°F (4°C) - 104°F (40°C)
39°F (4°C) - 104°F (40°C)
39°F (4°C) - 104°F (40°C)
Hardness (max.)
120 ppm (7 grains / gallon)
120 ppm (7 grains / gallon)
120 ppm (7 grains / gallon)
120 ppm (7 grains / gallon)
120 ppm (7 grains / gallon)
Iron (max.)
0.3 ppm
0.3 ppm
0.3 ppm
0.3 ppm
0.3 ppm
UVT (min.)
75%
75%
75%
85%
85%
Installation direction
Vertical
Vertical
Vertical
Vertical
Vertical
electrical
Voltage
120 - 240V AC
120 - 240V AC
120 - 240V AC
120 - 240V AC
120 - 240V AC
Engineered to
Frequency
50 - 60 Hz
50 - 60 Hz
50 - 60 Hz
50 - 60Hz
50 - 60Hz
Higher Standards
Max. current
1.2 Amp
1.6 Amp
2.4 Amp
2.4 Amp
2.4 Amp
Max. power consumption
120 Watts
160 Watts
230 Watts
230 Watts
230 Watts
Lamp power
100 Watts
140 Watts
200 Watts
200 Watts
200 Watts
dimensions
Chamber
22” x 4” (54 x 10 cm)
31” x 4” (78 x 10 cm)
41” x 4” (103 x 10 cm)
41” x 4” (103 x 10 cm)
41” x 4” (103 x 10 cm)
Power Supply
13” x 6.5” (33 x 16.5 cm)
13” x 6.5” (33 x 16.5 cm)
13” x 6.5” (33 x 16.5 cm)
13” x 6.5” (33 x 16.5 cm)
13” x 6.5” (33 x 16.5 cm)
Inlet & Outlet
Combo 1 1/4” NPT, 1” FNPT
Combo 1 1/4” NPT, 1” FNPT
Combo 1 1/4” NPT, 1” FNPT
2” MNPT
2” MNPT
Features
Colour coded plug
and play connections
Yes
Yes
Yes
Yes
Yes
CoolTouch fan / valve
Yes
Yes
Yes
Yes
Yes
Sensor with
diagnostic test
+ models
+ models
+ models
+ model
Yes
Solenoid Valve
Optional
Optional
Optional
Optional
Optional
Chamber material
316L SST
316L SST
316L SST
316L SST
316L SST
Communication Ports
(two, RJ45)
Yes
Yes
Yes
Yes
Yes
COMMcenter control package
Optional (+ model only)
Optional (+ model only)
Optional (+ model only)
Optional (+ model only)
Optional
Audible alarm mute button
Yes
Yes
Yes
Yes
Yes
Lamp reset button
Yes
Yes
Yes
Yes
Yes
Lamp age indicator
Yes
Yes
Yes
Yes
Yes
Lamp operation indicator
Yes
Yes
Yes
Yes
Yes
Power supply
operation indicator
Yes
Yes
Yes
Yes
Yes
Solenoid operation indicator
Yes
Yes
Yes
Yes
Yes
Fan operation indicator
Yes
Yes
Yes
Yes
Yes
Sensor Reading Output
Yes
Yes
Yes
Yes
Yes
Consumables
Lamp
602854
602855
602856
602856
602856
Quartz Sleeve
602974
602975
602976
602976
602976
G: 650709-001; 650645 - 120V;
H:650709-004; 650651 -
J:650709-007; 650657 - 120V;
K:66018-R; 660001-R - 120V;
660020-R; 660003-R - 120V;
650648 - 230V;
120V; 650654 - 230V ;
650660 - 230V;
660004-R - 230V;
660006-R - 230V
Power Supply
G Plus: 650709-002; 650646 -
H Plus: 650709-005; 650652 -
J Plus: 650709-008; 650658 -
K Plus 660019-R; 660002-R –
120 V; 650649 - 230V
120V; 650655 - 230V
120V; 650661 - 230V
120V; 660005-R – 230V
Sensor
650580
650580
65080
650580
650580
* Inlet/outlet size restricts flow to 45gpm and the dose will be 39mJ/cm 2
Warranty Please visit www.uvmax.com for the comprehensive warranty for our UVMAX TM product line.
425 Clair Rd. W, Guelph, Ontario, Canada N1L 1R1
t. (+1) 519.763.1032 • tf. 1.800.265.7246 (US and Canada only)
G, H, J, K & Pro50
f. (+1) 519.763.5069 • t. +31 73 747 0144 (Europe only)
e-mail: info@viqua.com www.viqua.com